Img_RFD-V_01_GBpng.png
250_RFD-V-Dxpng.png

Runder Frontdurchlass

RFD-V-1jpg.jpg

Runder Anschlusskasten

RFD-V_testpng.png

Innenliegender thermischer Stellantrieb

Img_RFD-V_01_GBpng.png
250_RFD-V-Dxpng.png
RFD-V-1jpg.jpg
RFD-V_testpng.png

RFD-V

With low sound power level for comfort and industrial zones, with fixed air control blades and variable internal geometry

  • Circular swirl diffusers for exposed ceiling installation
  • Nominal sizes 160, 200, 250, 315
  • Volume flow rate range 9l/s – 195l/s or 32m³/h – 702m³/h
  • For variable and constant volume flows
  • Available in RAL CLASSIC colours
  • Horizontal duct connection
  • Plenum box with damper blade and pressure tap
  • Internal thermal actuator to switch between rapid heating and cooling modes 

General Information

Application

  • Type RFD-V ceiling swirl diffusers are used as supply or extract air diffusers for comfort and industrial zones
  • Attractive design element for building owners and architects with demanding aesthetic requirements
  • Horizontal 360° supply air discharge for mixed flow ventilation
  • The efficient swirl creates high induction levels, thereby rapidly reducing the temperature difference and airflow velocity (supply air)
  • Designed for freely suspended applications
  • For variable and constant volume flows 
  • For supply air to room air temperature differences -10 to +15 K


Special characteristics

  • Low sound power level, ideal for comfort zones
  • Fixed blades
  • Diaphragm for volume flow determination 
  • Optional internal lining, closed or open cell
  • Internal thermal actuator (supply only)


Nominal sizes

  • 160, 200, 250, 315


Construction

Diffuser face finish



  • P3: Powder-coated RAL9010, pure white, gloss level 20%
  • P2: Powder-coated RAL9006, white aluminium, gloss level 30%
  • P4: Powder-coated RAL9005, jet black white, gloss level 20%
  • P6: Powder-coated in any other RAL CLASSIC colour, gloss level 30% 


Plenum finish



  • 0: Natural (unpainted)
  • P3: Powder-coated RAL9010, pure white, gloss level 20%
  • P2: Powder-coated RAL9006, white aluminium, gloss level 30%
  • P4: Powder-coated RAL9005, jet black, gloss level 20%
  • P6: Powder-coated in any other RAL CLASSIC colour, gloss level 30% 


Material and surfaces

  • Diffuser face made of galvanised steel
  • Discharge nozzle made of aluminium
  • Plenum box, non-visible adjustment mechanism and cross bar made of galvanised sheet steel


Standards and guidelines

  • Sound power level of the air-regenerated noise measured according to EN ISO 5135


Maintenance

  • Low maintenance as construction and materials are not subject to wear
  • Inspection and cleaning to VDI 6022

Technical information

Function, Technical data, Quick sizing, Specification text, Order code

  • Function
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
Schematic illustration of the RFD-V RFD-V_Schematicpng.png

1 Discharge nozzle 

2 Swirl element 

3 Air distribution element

4 Pressure Diaphragm

5 Retractable sleeve

6 Thermal actuator

7 Spigot damper

8 Lip seal

9 Pressure tap

Ceiling diffusers direct the air from air conditioning systems into the room. The resulting airflow induces high levels of room air, thereby rapidly reducing the airflow velocity and the temperature  difference between supply air and room air. Ceiling diffusers allow for large volume flow rates. The result is a mixed flow ventilation in comfort zones, with good overall room ventilation, creating only very little turbulence in the occupied zone. 


Type RFD-V ceiling diffusers have fixed blades and an adjustable internal sleeve, allowing for horizontal and vertical air discharge. During cooling air discharge is horizontal and radial, in heating air discharge is vertical. The internal sleeve is controlled with a thermal actuator. The supply air to room air temperature difference may range from -10 to +15K. To give rooms an aesthetic, uniform look. Type RFD-V diffusers may also be used for extract air. 

Nominal diffuser sizes160, 200, 250, 315

Minimum volume flow rate, with Δtz = -8K

9l/s - 32l/s or 32m3/h - 307m3/h

Maximum volume flow rate with LWA ≈ 50dB(A)

64l/s - 195l/s or 230m3/h - 702m3/h

Usage instructions


Please note that the minimum volume flows are not valid for free hanging or exposed installation. For these types of installation the minimum flow rate is equivalent to an effective discharge velocity of 3.5m/s


Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures. The minimum volume flow rates apply to a supply air to room air temperature difference of –6 K. The maximum volume flow rates apply to a sound power level of approx. 50 dB (A) with damper blade position 0°.

RFD-V-... (supply air), sound power level and total differential pressure.

Nominal size

qv [l/s]

qv [m³/h]

Ø SpigotDamper blade position
0⁰45⁰90⁰

Δpₜ [Pa]

LWA [dB(A)]

Δpₜ [Pa]

LWA [dB(A)]

Δpₜ [Pa]

LWA [dB(A)]

16020721586177161017
16033118.8158153119312731
16047169.2158314138415641
16060216158514861489148
20030108198517717917
20050180198143218322632
20070252198284236425142
20090324198465060508550
250501802485207201020
25080288248143419342634
250110396248264336435043
250140504248415058518150
31570252313520620919
315110396313123416332333
315150540313234330434242
315190684313365048506749

Specification text

Swirl diffusers with circular diffuser face. Supply and extract air variants for comfort zones and industrial zones. Diffuser face with fixed control blades and variable internal geometry controlled via thermal actuator. In cooling supply air will discharge in a horizontal swirling pattern creating high induction levels. In heating supply air will switch to vertical discharge to penetrate into the occupied zone.  For installation into all types of suspended ceilings and rooms without suspended ceilings. Ready-to-install component which consists of the diffuser face with radially arranged fixed air control blades and a plenum box with side entry, and suspension holes or suspension lugs. The diffuser face is fixed to the cross bar with a central screw. Thermal Actuator temperature range 18 °C to 32 °C. Spigot suitable for ducts to EN 1506 or EN 13180. Sound power level of the air-regenerated noise measured according to EN ISO 5135.



Note: Cooling supply air temperature of <22°C required to reset the thermal actuator



Note: Vertical heating requires supply air temperature of >28°C


Parts and characteristics

  • Circular diffuser face 
  • Diffuser with radially arranged fixed air control blades 
  • Simple installation of the diffuser due to central rivnut
  • Damper blade for volume flow rate balancing 


Materials and surfaces

  • Diffuser face made of galvanised steel
  • Discharge nozzle made of aluminium
  • Plenum box, non-visible adjustment mechanism and cross bar made of galvanised sheet steel
  • P2: Powder-coated RAL 9006: 30 %
  • P3: Powder-coated RAL 9010: 20 %
  • P4: Powder-coated RAL 9005: 20 %
  • P6: Powder-coated RAL CLASSIC colour 30 % gloss


Technical data

  • Nominal diffuser sizes: 160, 200, 250, 315
  • Minimum volume flow rate, with Δtz = -8K: 9l/s – 32l/s or 32m³/h – 307m³/h
  • Maximum volume flow rate with LWA ≈ 50dB(A): 64l/s –  195l/s or 230m³/h – 702m³/h  


Usage instructions

  • Please note that the minimum volume flows are not valid for free hanging or exposed installation. For these types of installation, the minimum flow rate is equivalent to an effective discharge velocity of 3.5m/s

RFD-VZDXD12MLADE/200×198/SB/P3P6 - RAL 9016
||||||||||||
123456789101112
1 Type
RFD-V Swirl diffuser

2 System
Z Supply air
A Extract air

3 Construction
DX Standard

4 Inner lining (insulation)
No entry: without lining
D06 inner lining 6 mm thick
D12 inner lining 12 mm thick

5 Spigot damper for flow rate balancing
M with damper screen

6 Lip seal
No entry: without lip seal
L with lip seal

7 Air distribution element
No entry: without air distribution element
ADE with air distribution element

8 Nominal size [mm]
160, 200, 250, 315

9 Spigot diameter [mm]

158 (only for nominal size 160)
198 (only for nominal size 200, 250)
248 (only for nominal size 200, 250, 315)
313 (only for nominal size 315)

10 Plenum box fixing
No entry: central threaded rod
SB Fixing bracket

11 Exposed surface of diffuser face
P2 powder-coated RAL 9006 (white aluminium)
P3 powder-coated, RAL 9010 (pure white)
P4 powder-coated, RAL 9005 (deep black)
P6 powder-coated, specify RAL CLASSIC colour

12 Surface plenum box
No entry: without surface finish
P2 powder-coated RAL 9006 (white aluminium)
P3 powder-coated, RAL 9010 (pure white)
P4 powder-coated, RAL 9005 (deep black)
P6 powder-coated, specify RAL CLASSIC colour

Gloss level
RAL 9006 GU 30
RAL 9010 and RAL 9005 GU 20
All other RAL colours GU 30Order example: RFD-V-Z-DX-D12-M-L/200×198/SB/P3-P6-RAL9016
TypeRFD-V – swirl diffuser
Systemsupply air
Constructionstandard
Inner lining (insulation)inner lining 12 mm thick
Spigot damper for volume flow rate balancingwith spigot damper 
Lip sealwith lip seal
Air distribution elementwith air distribution element
Nominal size [mm]200
Spigot diameter [mm]198
Plenum box fixingfixing brackets
Exposed surface of diffuser facepowder-coated, RAL 9010 (pure white)
Surface plenum boxpowder-coated, RAL 9016 (traffic white)

Product details

  • Product details

Product details

RFD-V NS

160 

200 

250 

315 

Ceiling cutout Ød [mm]

299346397551

Thermal actuator function


The RFD-V switches between horizontal and vertical discharge depending on supply air temperature, via a thermal actuator. The diffuser will switch from horizontal discharge to vertical discharge once the supply temperature reaches above 28⁰C. The diffuser will switch back to horizontal discharge from vertical discharge once the supply temperature reaches below 22⁰C.

Volume flow rate balancing


When several diffusers are connected to just one volume flow controller, it may be necessary to balance the volume flow rates. 


Ceiling diffusers with plenum box and damper blade


  • The diffuser face can be removed to access the damper blade
  • The damper blade can then be set to any position between 0 and 90°, the damper blade can also be adjusted externally using the cam on the spigot. 


Volume flow rate measurement


Ceiling diffusers with horizontal plenum box, damper blade and pressure diaphragm allow for volume flow rate balancing with the diffuser face in place.


  • Connect the pressure tap to the digital manometer
  • Read the effective pressure
  • Read the volume flow rate off the characteristic or calculate it
  • If necessary, adjust the damper blade position

Downloads

product information

certificates

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Contact

We are here for you

Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051