Conforms to VDI 6022
SEH Single room exhaust air
SRO Single room outdoor air
SRS Single room supply air
SET Single room extract air
SEC Secondary air (optional)
1 Outdoor air temperature sensor (optional)
2 Shut-off damper with actuator (exhaust air and outdoor air)
3 Fine dust filter ISO ePM1 for outdoor air
4 EC fan (supply air and extract air)
5 Cross-counterflow heat recovery unit
6 Sound attenuator
7 Heat exchanger
8 Supply air temperature sensor (optional)
9 Bypass damper with actuator (modulating)
10 CO2 sensor (optional)
11 Extract air filter ISO coarse
Functional description
Decentralised supply and extract air units ventilate the room and cover the cooling and heating load in accordance with the technical data. The outside air is drawn in by an EC centrifugal fan and flows through the motorised shut-off damper and the outdoor air filter. The outdoor air then flows through the crosscounterflow heat recovery unit, which can be switched off in energy-efficient operating situations and to protect the device. Before the supply air flows into the room like displacement air, it is heated or cooled in the heat exchanger if required (changeover).
The extract air first flows through the extract air filter, before it is discharged to the outside as exhaust air, by passing the heat recovery unit, the extract air fan and the motorised shut-off damper.
If the indoor air quality is sufficient, the FSL CONTROL III control system switches to energy-efficient secondary air mode by closing the outdoor air dampers. The control system compares the room air quality setpoints to the actual values measured by the CO2sensor and switches automatically between outdoor air and secondary air operation. In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection and to avoid draughts. This is ensured by a capacitor in each actuator. Close to the façade, the supply air is discharged into the room with a medium velocity between 0.5 and 0.8 m/s. Due to the induction effect, the supply air velocity is rapidly reduced so that, in cooling mode, the supply air spreads across the entire floor area as a displacement flow. Near heat sources such as people or equipment, a buoyancy flow is formed by natural convection, so that the air is exchanged primarily in these areas.
Width | 600 mm |
Height | 2000 mm |
Depth | 408 mm |
Volume flow rate | 150, 200, 240 m³/h (boost 360 m³/h) |
Nominal volume flow rate | 240 m³/h |
Sound power level | 36 – 50 dB(A) |
Heat recovery efficiency | 84 % |
Maximum operating pressure, water side | 6 bar |
Maximum operating temperature | 75 °C |
Supply voltage | 1~ 230 V AC, ±10 %, 50/60 Hz |
Power rating | 592 VA |
Weight | 90 kg |
| SA-V | HE | 2 | 1 | KM | 600 × 2000 × 408 | C3 | MA | T | MR | C | Z | A | HV | R | 0,40 | ||||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 |
1 Type
SA-V vertical decentralised ventilation unit X-CUBE/ SCHOOLAIR-V
2 Variant
HE High heat recovery efficiency
3 Heat exchanger
2 2-pipe
4 Heat exchanger construction
Specify construction (technical design with TROX EPF or TROX CONFIGURATOR)
5 Construction
KM with condensate drain
6 Nominal size [mm]
Width × height × depth
600 × 2000 × 408
7 Control system
OR without control system
C3 with FSL-CONTROL III
8 Control function
MA Master
SL Slave
9 Real-time clock
Only with control function MA
No entry: without real time clock
T with real time clock
10 Interface
No entry: without interface
MT with Modbus TCP
MR with Modbus RTU (only with control function MA)
BI with BACnet IP
BM with BACnet MS/TP (only with control function MA)
11 Air quality sensor
Only with control function MA
No entry: without air quality sensor
C with CO2 sensor
V with VOC sensor
12 Supply air temperature sensor
Z with supply air temperature sensor
13 Outdoor air temperature sensor
Only with control function MA
No entry: without outdoor air temperature sensor
A with outdoor air temperature sensor
14 Heating valve
HV with thermoelectric actuator
HVE with electromotive actuator
15 Lockshield – heating circuit
R with lockshield valve
16 Kvs value heating valve
0.25 (straight-way valve)
0.40 (straight-way valve)
0.63 (straight-way valve)
1.00 (straight-way valve)
F0.50 (pressure-independent control valve)
Order example: SA-V-HE-2-1-KM/600×2000×408/C3-MA-T/MR/C/Z/A/HV-R-0.40
| Type | SA-V | Vertical decentralised ventilation unit X-CUBE/SCHOOLAIR-V |
| Variant | HE | High heat recovery rate |
| Heat exchanger | 2 | 2-pipe |
| Heat exchanger construction | 1 | Heat exchanger type 1 |
| Construction | KM | with condensate drain |
| Nominal size [mm] | 600×2000×408 | Width 600, height 2000, depth 408 |
| Control system | C3 | with FSL-CONTROL III |
| Control function | MA | Master |
| Real time clock | T | with real time clock |
| Interface | MR | with Modbus RTU |
| Air quality sensor | C | with CO2 sensor |
| Supply air temperature sensor | Z | with supply air temperature sensor |
| Outdoor air temperature sensor | A | with outdoor air temperature sensor |
| Heating valve | HV | with thermoelectric actuator |
| Lockshield – heating circuit | R | with lockshield |
| Kvs value – heating valve | 0.40 | 0.40 (straight-way valve) |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051
Contact
We are here for you
Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051