FK2-EU 

FOR DIVERSE APPLICATIONS 


  • Nominal sizes 200 × 100 to 1500 × 800 mm, in increments of 1 mm
  • Low differential pressure and sound power level
  • Explosion-proof construction (ATEX) as an option
  • Can also be used as an air transfer unit
  • Optional stainless steel casing or powder-coated casing for increased corrosion protection
  • Integration into the central BMS with TROXNETCOM
  • Universal installation options


Optional equipment and accessories

  • Electric actuator 24 V/230 V
  • Release temperature 72/95 °C

 

Useful additions

  • Duct smoke detectors

General information

Application

  • Fire dampers with CE marking and declaration of performance, for the isolation of duct penetrations between two fire compartments in the event of a fire
  • To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments


Special characteristics

  • Declaration of performance in accordance with European Construction Products Regulation
  • Classification according to EN 13501-3, to EI 120
    (ve, ho, i ↔ o) S
  • Complies with the requirements of EN 15650
  • Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
  • Certified mortar-based installation with reduced distances of 40 mm to supporting components or 60 mm between two fire dampers (flange to flange)
  • Perimeter gap may be up to 225 mm for mortar-based installation
  • 2 inspection accesses with bayonet fixing for single-handed operation
  • Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 2
  • Casing air leakage to EN 1751, class C (B + H ≤700, class B)
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central building management system with the international standard fire damper system in accordance with IEC 62026-2 with AS interface is possible


Classification

  • Leistungsklasse bis EI 120 (ve , ho , i ↔ o) S nach EN 13501-3


Nominal sizes

  • B × H: 200 × 100 – 1500 × 800 mm (intermediate sizes in increments of 1 mm)
  • L: 305 mm or 500 mm


Variants

  • With fusible link
  • With spring return actuator
  • With spring return actuator and duct smoke detector
  • With cover grille on both sides as an air transfer unit


The following applies to Germany:
If fire dampers with a purely mechanical shut-off element are to be used as an air transfer unit, the local building regulations must be observed. Usually the use of such air transfer units is restricted to pressure differential systems.


Parts and characteristics

  • Release temperature 72 °C or 95 °C (for use in warm air ventilation systems)
  • Single-handed operation
  • Explosion-proof constructions for zones 1, 2, 21, 22


Attachments

  • Limit switch for damper blade position indication
  • Spring return actuator for 24 V AC/DC or 230 V AC supply voltage
  • Limit switch for damper blade position indication for use in potentially explosive atmospheres
  • Spring return actuator for 24 – 230 V supply voltage, for use in potentially explosive atmospheres
  • Network module for the integration with AS-i or LON networks
  • Spring return actuator and wired duct smoke detector, 24 V DC or 230 V supply voltage
  • All attachments can be retrofitted


Accessories

  • Installation kit GM for installation into solid non-load-bearing walls with flexible ceiling joint
  • Installation kit ES for dry mortarless installation in lightweight partition walls or compartment walls with metal support structure and cladding on both ends
  • Installation kit GL for dry mortarless installation in lightweight partition walls or compartment walls with metal support structure, cladding on both sides and flexible ceiling joint
  • Installation kit ES for dry mortarless installation into timber stud walls / half-timbered constructions and solid wood walls
  • Installation kit ES for dry mortarless installation into shaft walls with or without metal support structure but with cladding on one side
  • Installation kit WE for dry mortarless installation remote from solid walls, remote from solid ceiling slabs, and remote from lightweight partition walls with metal support structure and cladding on both sides
  • Installation kit WA for dry mortarless installation on the face of solid walls and ceiling slabs
  • Installation kit ES for dry mortarless installation in wooden beam ceilings and solid wood ceilings
  • Flexible connectors
  • Cover grille
  • Circular spigots
  • Profile connecting frame


Useful additions

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D


Construction features

  • Rectangular or square construction, rigid casing, both flanges with fixing holes
  • Suitable for the connection of ducts, cover grilles, spigots, flexible connectors or profile connecting frames
  • The release mechanism is accessible and can be tested from the outside
  • 2 inspection access panels, Ø110 mm, which can be opened without any tools
  • Remote control with spring return actuator


Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:

  • Special insulation material
  • Special insulation material with coating


Other components:

  • Damper blade shafts and drive linkage made of galvanised steel, in constructions -1 and -2 made of stainless steel
  • Plastic bearings
  • EPDM and TPE seals


The construction variants with stainless steel or powder-coated casing meet even more critical requirements for corrosion protection. Detailed listing on request.


Standards and guidelines

  • Construction Products Regulation
  • EN 15650 Ventilation for buildings – Fire dampers
  • EN 1366-2 Fire resistance tests for service installations – Fire dampers
  • EN 13501 Fire classification of construction products and building elements
  • EN 1751 Ventilation for buildings – Air terminal devices

Supply package

If attachments and accessories are factory set with the fire dampers, they are already included in the order code. Installation situations may require supplementary materials for assembly and fixing, such as mortar, screws, mineral wool, etc., to ensure correct installation. Such materials are not included in the scope of delivery, unless they are expressly described as part of the delivery. The selection of supplementary attachments or accessories as well as the determination and provision of materials for assembly and fixing is the responsibility of the parties involved in the construction and must be carried out taking into account the desired classification. 

Maintenance

  • The functional reliability of the fire damper must be tested at least every six months; this has to be arranged by the owner of the ventilation system; functional tests must be carried out in compliance with the basic maintenance principles stated in EN 13306 and DIN 31051. If two consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later. If 2 consecutive tests, one 6 months after the other, are successful, the next test can be conducted one year later
  • A functional test involves closing the damper blade and opening it again; with a spring return actuator this can be done via remote control
  • Fire dampers must be included in the regular cleaning schedule for the ventilation system
  • For details on functional tests, maintenance and inspection refer to the installation and operating manual


Technical data

  • Nominal sizes: 200 × 100 to 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 14400 l/s / up to 51840 m³/h
  • Differential pressure: up to 2000 Pa
  • Temperature range: -20 – 50 °C
  • Upstream velocity*: ≤ 8 m/s with standard construction; ≤ 12 m/s with spring return actuator


* Data applies to uniform upstream and downstream conditions for the fire damper


Incorrect use:

  • without specially approved attachments in areas with potentially explosive atmospheres
  • as a smoke control damper
  • outdoors without sufficient protection against the effects of weather
  • in atmospheres where chemical reactions, whether planned or unplanned, may cause damage to the fire damper or lead to corrosion


The following applies to installation in Germany:

  • Do not use it in extract air systems in commercial kitchens
  • Do not use in combined penetration seal
  • Approvals under building regulations may be required for the use of air transfer units. This must be checked and applied for by others.
  • Flame-resistant building materials that form no dripping droplets (elastomer foams) have to be at least of fire rating class C - s2, d0 according to the German M‑VV TB (2019/1) guideline. The applicable national building regulations must be adhered to

Technical information

Function, Technical Data, Quick sizing, Specification Text, Order Code

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

 

 


Nominal sizes200 × 100 – 1500 × 800 mm ⁴
Casing lengths305 and 500 mm
Volume flow rate rangeup to 14400 l/s or 51840 m³/h
Differential pressure rangeUp to 2000 Pa

Temperature range 1, 3

-20 to 50 °C
Release temperature72 °C or 95 °C (for warm air ventilation systems)
Upstream velocity ²

Standard construction ≤ 8 m/s,
Construction with spring return actuator ≤ 12 m/s,
Construction with explosion-proof actuator ExMax/RedMax-15-BF TR ≤ 10 m/s



¹ Temperatures may differ for units with attachments. Details for other applications are available on request.
² Data applies to uniform upstream and downstream conditions for the fire damper.
³ Condensation and the intake of humid fresh air have to be avoided as otherwise operation will be impaired or not be possible.
⁴ Damper blade with lip seal for sizes 1 and 2, damper blade with travel stop seal for size 3.

Sizes see functional description


Free area and resistance coefficient, width 200 – 800 mm

H [mm]B [mm]
200250300350400450500550600650700750800
100A [m²]0.0130,0160.0200,0230.0270,0300.0340,0370.0410,0440.0480.0510.055
100ζ1.050,960.880,830.780,750.710,690.660,640.620.610.59
125A [m²]0.01750,02220.0270,03170.03650,04120.0460,05070.05550,06020.0650.06970.0745
125ζ0.930,850.780,730.690,660.630,610.590,570.550.540.52
150A [m²]0.02210,02810.03410,04010.04610,05210.05810,06410.07010,07610.08210.08810.0941
150ζ0.850,770.710,670.630,600.580,550.540,520.500.490.48
160A [m²]0.0240,0300.0370,0430.050,0560.0630,0690.0760,0820.0890.0950.102
160ζ0.660,600.550,520.490,470.450,430.410,400.390.380.37
200A [m²]0.0310,0400.0480,0570.0650,0740.0820,0910.0990,1080.1160.1250.133
200ζ0.740,670.620,580.550,520.500,480.470,450.440.430.41
250A [m²]0.03970,05070.06170,07270.08370,09470.10570,11670.12770,13870.14970.16070.1717
250ζ0.670,610.560,530.500,470.450,440.420,410.400.380.37
300A [m²]0.04890,06240.07590,08940.10290,11640.12990,14340.15690,17040.18390.19740.2109
300ζ0.620,560.520,490.460,440.420,400.390,380.360.350.34
350A [m²]0.05810,07410.09010,10610.12210,13810.15410,17010.18610,20210.21810.23410.2501
350ζ0.580,520.480,450.430,410.390,380.360,350.340.330.32
400A [m²]0.06730,08580.10430,12280.14130,15980.17830,19680.21530,23380.25230.27080.2893
400ζ0.540,490.460,430.400,390.370,350.340,330.320.310.30
450A [m²]0.07650,09750.11850,13950.16050,18150.20250,22350.24450,23550.25480.27410.2934
450ζ0.570,510.470,430.410,390.370,350.340,330.320.310.30
500A [m²]0.08570,10920.13270,15620.17970,20320.22670,25020.27370,2660.28780.30960.3314
500ζ0.540,480.440,410.390,370.350,340.330,310.300.300.29
550A [m²]0.12640,15070.1750,19930.22360,24790.27220,29650.32080.34510.3694
550ζ0.420,400.370,350.340,320.310,300.290.280.28
600A [m²]0.13940,16620.1930,21980.24660,27340.30020,3270.35380.38060.4074
600ζ0.410,380.360,340.320,310.300,290.280.270.27
650A [m²]0.15240,18170.2110,24030.26960,29890.32820,35750.38680.41610.4454
650ζ0.390,370.350,330.310,300.290,280.270.260.26
700A [m²]0.16540,19720.2290,26080.29260,32440.35620,3880.41980.45160.4834
700ζ0.380,350.330,320.300,290.280,270.260.250.25
750A [m²]0.17840,21270.2470,28130.31560,34990.38420,41850.45280.48710.5214
750ζ0.370,340.320,310.290,280.270,260.250.250.24
800A [m²]0.19140,22820.2650,30180.33860,37540.41220,4490.48580.52260.5594
800ζ0.360,330.320,300.290,270.260,260.250.240.23

① Parameter 



Free area and resistance coefficient, width 850 – 1500 mm

H [mm]B [mm]
900100011001200130014001500
200A[m²]0.1170.16650.14420.15780.17140.1850.1986
200ζ0.440.420.400.390.380.360.35
250A[m²]0.160.21570.19720.21580.23440.2530.2716
250ζ0.390.370.350.340.330.320.31
300A[m²]0.2030.26490.25020.27380.29740.3210.3446
300ζ0.350.340.320.310.300.290.28
350A[m²]0.2460.27460.30320.33180.36040.3890.4176
350ζ0.320.310.300.290.280.270.26
400A[m²]0.2890.32260.35620.38980.42340.4570.4906
400ζ0.300.290.280.270.260.250.25
450A[m²]0.3320.37060.40920.44780.48640.5250.5636
450ζ0.290.280.260.260.250.240.23
500A[m²]0.3750.41860.46220.50580.54940.5930.6366
500ζ0.270.260.250.240.240.230.22
550A[m²]0.4180.46660.51520.56380.61240.6610.7096
550ζ0.260.250.240.230.230.220.21
600A[m²]0.4610.51460.56820.62180.67540.7290.7826
600ζ0.250.240.230.220.220.210.20
650A[m²]0.5040.56260.62120.67980.73840.7970.8556
650ζ0.240.230.220.220.210.200.20
700A[m²]0.5470.61060.67420.73780.80140.8650.9286
700ζ0.240.230.220.210.200.200.19
750A[m²]0.590.65860.72720.79580.86440.9331.0016
750ζ0.230.220.210.200.200.190.19
800A[m²]0.6330.70660.78020.85380.92741.011.0746
800ζ0.220.210.200.200.190.190.18

① Parameter 



Quick sizing tables provide a good overview of the volume flow rates with different sound power levels as well as of differential pressures of up to 35 Pa. Approximate intermediate values can be interpolated. Precise intermediate values can be calculated with our Easy Product Finder design program.

Volume flow rate qv for differential pressure Δpst < 35 Pa
200 – 650 mm

H [mm]LWA [dB(A)]B [mm]
200250300350400450500550600650
10035390484577668759849938102711161205
1253550762774586297810931208132214351548
150356197649071048118813261464160117371873
1603572889710631227139015501710186920272185
20035835102812161402158617691950213023092487
250351026126414961725195121742396261628353053
300351232151217862056232125842844310333603615
350351434175720712379268329843281357738704161
400351634199723512698303933773710404143694696
450351474185622252585293832863629396943054640
500351647207124802878326936524031440647785146
5503527333169359540154429483852435645
6003529833456391943744823526657046139
6503532323742424147305213568961606627
7003534794026456050845600610966137112
7503537254308487754355984652670627592
8003539704589519357846367694175088070


Volume flow rate qv for differential pressure Δpst < 35 Pa
700 – 1500 mm

H [mm]LWA [dB(A)]B [mm]
700750800900100011001200130014001500
10035129313801468
12535166017721883
15035200821422276
16035234124972653
200352664284130172633291531963476375440314308
250353270348637013422378541474506486452215576
300353869412243744172461150485482591563456774
350354451473950274895540659146419692274237922
400355020534356645597617767537327789784659031
4503549725302563062826929757282118847948010110
50035551258756237695576678374907797761047111164
550356044644068347616839291629926106871144412198
6003565706998742482699107993810763115841240113214
65035709175518008891498131070411589124691334414216
700357606809885859553105111146112405133431427615204
7503581188640915810186112031221113213142081519716181
8003586269178972710813118891295514013150641610917149


Volume flow rate qv for differential pressure Δpst < 35 Pa
200 – 650 mm

H [mm]LWA [dB(A)]B [mm]
200250300350400450500550600650
10045525690841975110712391369149916291758
1254571087010881258142715951762192820942258
15045880111513231529173319352136233625342732
160451063130915521791202822622496272729583188
200451219149917752046231425802845310733683628
250451498184421832517284631733496381841374455
300451797220726072999338737704150452749025274
350452092256330223472391543544788521856466071
400452384291534313937443549275413589663756851
450452151270932473772428747945295579062826769
500452404302236194200476953295882642969717508
5504539874623524658586462705976508237
6004543535043571863827036768383228957
6504547155460618769027605830089889669
70045507658746653741881708913964810376
750455435628671167930873195221030311077
8004557926695757684409289101271095411774


Volume flow rate qv for differential pressure Δpst < 35 Pa
700 – 1500 mm

H [mm]LWA [dB(A)]B [mm]
700750800900100011001200130014001500
10045188620142142
12545242225852748
15045292931263322
16045341636443871
200453887414544023842425446635071547758826285
250454771508654004993552360506575709776178136
300455645601463826088672873657999863092589884
350456494691573347142788886299366101001083011558
4004573247795826481669012985310690115221235113177
450457254773582149166101101104811980129081383114751
5004580428572910010147111861221713243142631527816289
5504588189397997111113122441336714483155931669717797
600459586102111083212065132871449915704169021809319280
6504510345110161168313006143171561716908181921947020741
7004511098118141252613938153361672218099194672082822183
7504511844126061336214861163451781619277207292217223609
8004512586133911419115777173461890120444219782350325020

Fire damper in line with the European product standard DIN EN 15650 in square or rectangle construction style with 2 large inspection accesses that can be operated without tools. Tested for fire resistance properties according to DIN EN 1366-2 (300 Pa and 500 Pa negative pressure), with CE label.

The fire damper manufacturer's declaration of performance (DoP) provides proof that a product is suitable for the respective installation conditions, e.g. in, on the face of and remote from walls or ceilings, with the stated essential characteristics such as size, supporting construction, construction and installation type, and that it has the corresponding class of performance to EN 13501-3.
The ready-for-operation unit includes a release mechanism and a replaceable, fire-resistant damper blade, which, depending on the application, can be either horizontal or vertical. Depending on application, classified from: 
EI 30 (ve, ho i ↔ o) S to EI 120 (ve, ho i ↔ o) S



Suitable for:

Mortar-based installation

  • In solid walls, walls made from gypsum wall boards, lightweight partition walls, compartment walls, safety partition walls and walls to provide radiation protection
  • With installation kit for flexible ceiling joints in solid walls
  • In shaft walls with metal support structures or steel support structures
  • In timber stud walls and timber frame walls, as well as solid wood and cross laminated timber walls
  • In and on solid walls and in combination with timber beam, solid wood and modular ceilings (System Cadolto)
  • In solid wood ceilings, wooden beam ceilings and historical wooden beam ceilings
  • If several fire dampers are installed in a solid wall or ceiling slab, their combined area must not exceed 3 m²
  • Can be installed together with FKRS-EU and FKR-EU in solid walls and ceiling slabs, lightweight partition walls and shaft walls
  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structures or steel support structures


Dry mortarless installation

  • In lightweight partition walls and compartment walls with metal support structure and cladding on both sides, and with flexible ceiling joint
  • In timber stud walls and timber frame walls, as well as solid wood and cross laminated timber walls

 

  • In shaft walls with metal support structure or steel support structure, and in shaft walls without metal support structure
  • In solid wood and wooden beam ceilings
  • With an installation kit on the face of and remote from solid walls and ceiling slabs
  • Remote from lightweight partition walls (wall penetration)


Fire batt installation

  • In solid walls and ceiling slabs
  • In lightweight partition walls, compartment walls, safety partition walls and walls to provide radiation protection, with metal support structure or steel support structure
  • In timber stud walls, half-timbered constructions, solid wood walls and CLT walls


Sizes from (B x H) 200 mm x 100 mm to 1500 mm x 800 mm, intermediate sizes in increments of 1 mm.
Optimised low-leakage casing, up to leakage class C to EN 1751 with low differential pressure and low sound power level.
Fire damper casing made of galvanised sheet steel, optionally galvanised sheet steel with powder coating RAL 7001 or stainless steel 1.4301.
Damper blade made of special insulation material; coating as an option
Corrosion protection according to EN 15650 in connection with EN 60068-2-52. Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI Casing length 305 mm or 500 mm with a 30 mm (L = 500 mm) flange for the connection to ducts made of non-combustible or combustible materials. Thermal release at 72 °C or 95 °C (warm air ventilation systems) with a fusible link or thermoelectrically with a spring return actuator, push button and indicator light (LED). Constructions with a brushless actuator for opening and closing the fire damper, also when the ventilation system is running and independent of the nominal size, are particularly suitable for functional checks and for shutting off sections of the duct system. The designs with brushless spring return actuators for opening and closing the fire damper – also when the ventilation system is running and independent of the nominal size – are particularly suited for function testing or the daily shut-off of cable sections.

Explosion-proof constructions for zones 1, 2, 21 and 22 available with limit switch or spring return actuator.


Special characteristics

  • Declaration of performance in accordance with European Construction Products Regulation
  • Classification according to EN 13501-3, to EI 120
    (ve, ho, i ↔ o) S
  • Complies with the requirements of EN 15650
  • Tested for fire resistance properties in accordance with EN 1366-2 (300 Pa and 500 Pa negative pressure)
  • Certified mortar-based installation with reduced distances of 40 mm to supporting components or 60 mm between two fire dampers (flange to flange)
  • Perimeter gap may be up to 225 mm for mortar-based installation
  • 2 inspection accesses with bayonet fixing for single-handed operation
  • Meets the hygiene requirements of VDI 6022-1, VDI 3803-1, DIN 1946-4, EN 13779, of Ö-Norm H 6020 and H 6021, and of SWKI
  • Corrosion protection according to EN 15650 in connection with EN 60068-2-52
  • Closed blade air leakage to EN 1751, class 2
  • Casing air leakage to EN 1751, class C (B + H ≤700, class B)
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the central building management system with the international standard fire damper system in accordance with IEC 62026-2 with AS interface is possible


Materials and surfaces

Casing:

  • Galvanised sheet steel
  • Galvanised sheet steel, powder-coated RAL 7001
  • Stainless steel 1.4301


Damper blade:

  • Special insulation material
  • Special insulation material with coating


Other components:

  • Damper blade shafts and drive linkage made of galvanised steel, in constructions -1 and -2 made of stainless steel
  • Plastic bearings
  • EPDM and TPE seals


Technical data

  • Nominal sizes: 200 × 100 to 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 14400 l/s / up to 51840 m³/h
  • Differential pressure: up to 2000 Pa
  • Temperature range: -20 – 50 °C
  • Upstream velocity: ≤ 8 m/s with standard construction; ≤ 12 m/s with spring return actuator


Equivalence criteria

  • The declaration of performance according to the Construction Products Regulation describes all CE-certified installation types including the performance class up to EI 120 S according to EN 13501-3 as well as the essential characteristics of at least the

  • Hygienic requirements are fulfilled in accordance with VDI 6022-1, VDI 3803-1, DIN 1946-4, DIN EN 13779 as well as the Önorm H 6020 and H 6021 and the SWKI.

  • CE-marked and thus tested for fire protection according to EU regulation 305/2011 and evaluated according to machinery directive 2006/42/EC
  • CE-certified mortar-based installation at a distance ≥ 60mm between 2 fire dampers (flange to flange)
  • Combined mortar-based installation with circular fire dampers in solid walls, lightweight partition walls clad on both sides and shaft walls with metal stud system with cladding on one side
  • 2 inspection access panels Ø110 mm, with bayonet fixing (can be opened without tools)

  • Pressure loss < 15 Pa at reference size 400 × 200 mm and 6 m/s face velocity

  • Sound power < 38 dB (A) at reference size 400 × 200 mm and 6 m/s face velocity



Order code FK2-EU



FK2-EU1 – 7 / DE / 600 × 400 × 500 / ES / A0 / Z43
|||||||
1234567


1 TypeFK2-EU
Fire damper
 

2 Construction
No entry: standard construction
powder-coated casing, RAL 7001
2 Stainless steel casing
7 coated damper blade

1 – 7 powder-coated casing, RAL 7001, and coated damper blade

2 – 7 Stainless steel casing and coated damper blade

W2) with fusible link 95 °C (only for warm air ventilation systems)B3) with coated fusible link 72 °C
WB3) with coated fusible link 95 °C (only for warm air ventilation systems) 

3 Country of destination
DE Germany
AT Austria

CH Switzerland

NL Netherlands 

4 Nominal size [mm]

B × H × L 

5 Accessories 1

No entry: none

ES1)

GM1.2)
WA1)
WE1)
GL1001.2)

GL1251.2)
GL1501.2)
GL1751.2) 

6 Accessories 2
No entry: none
0A – FR 


7 Attachments

Z00 – ZA14 

1)
Only for FK2-EU with L = 500 mm
2) Not combinable with Z...RM and ZA12

3) Only for attachments Z00 - Z03 and Z00EX - Z03EX


Order example: FK2-EU-W/DE/600×200×500/ES/A0/Z43
Construction variantCasing (galvanised)
Release temperature95 °C
Country of destinationGermany
Nominal size600 × 200 × 500 mm
Accessories 1Installation kit ES
Accessories 2Cover grille on operating side
AttachmentSpring return actuator 230 V AC
 
Note: For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.


Order code FK2-EU as an air transfer unit



FK2-EU1 – 7 / DE / 200 × 200 × 500 / ES / AA / Z03
|||||||
1234567



1 Type

FK2-EU Fire damper 

2 Construction
No entry: standard construction
powder-coated casing, RAL 7001
2 Stainless steel casing7 coated damper blade
1 – 7 powder-coated casing, RAL 7001, and coated damper blade
2 – 7 Stainless steel casing and coated damper blade 

3 Country of destination
upon request 

4 Nominal size [mm]
B × H × L 

5 Accessories 1
No entry: none
ES 


6 Accessories 2
AA Cover grilles on both ends 

7 Attachments
Z00 - ZB01 

For installation in Germany please note the following applies when used as air transfer unit: If a fire damper with only a mechanical shut-off element is to be used as an air transfer unit, the local building regulations apply. This may require building authority approvals. This must be checked and applied for by others. Usually the use of such air transfer units is restricted to pressure differential systems.



Order example: FK2-EU/DE/200×200×500/AA/Z03
Construction variantCasing (galvanised)
Country of destinationGermany
Nominal size200 × 200 × 500 mm
Accessories 1None
Accessories 2Cover grilles on both ends
AttachmentLimit switches display OPEN and CLOSED

Dimensions

  • DIMENSIONS
H [mm]B [mm]
200300400500600700800900100011001200130014001500
1004/55/66/87/98/119/1210/13
1504/65/77/98/109/1210/1311/15
2005/76/87/109/1210/1311/1512/1615/2016/2121/2723/2924/3126/3227/34
2507/98/1010/1211/1412/1614/1815/1916/2118/2324/2925/3127/3329/3530/38
3008/109/1211/1412/1513/1715/1916/2118/2319/2526/3228/3430/3632/3933/41
3508/1110/1311/1513/1715/1816/2018/2224/2926/3228/3430/3732/3934/4236/44
4009/1111/1312/1614/1816/2017/2219/2426/3128/3431/3733/3935/4237/4539/47
45010/1211/1413/1715/1917/2123/2826/3128/3430/3633/3935/4238/4540/4843/50
50010/1312/1514/1816/2018/2225/3027/3330/3633/3935/4236/4540/4843/5146/54
55015/1918/2221/2624/2826/3229/3532/3835/4137/4440/4743/5146/5449/57
60016/2019/2322/2725/3028/3331/3734/4037/4340/4743/5046/5349/5752/60
65017/2120/2523/2827/3230/3533/3936/4239/4642/4945/5348/5651/6055/63
70018/2221/2625/3028/3331/3735/4138/4441/4844/5248/5551/5954/6358/67
75019/2322/2726/3129/3533/3936/4340/4743/5047/5450/5854/6257/6661/70
80020/2424/2827/3331/3634/4038/4442/4945/5349/5753/6156/6560/6964/73

Accessories and Attachements

  • Accessories and Attachements



Accessories 1 - Installation kits

Installation kit GM

  • Installation into solid non-load-bearing internal walls with flexible ceiling joint requires an installation kit
  • With the installation kit the fire damper may be installed just below the movement joint; the joint is not interrupted by the installation kit
  • The mineral wool used for the flexible joint can also be used above the fire damper; s ≤ 30 mm after the ceiling has subsided
  • The fire damper is mortared in together with the installation kit on three sides
  • Fire dampers with installation kit only with casing length
    L = 500 mm
  • Installation only with horizontal damper blade
  • The fire damper and the installation kit must be installed and secured according to the operating and installation manual.

Note:
For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

L [mm]

Order code

500

GM

Installation kit ES

  • Universally applicable installation kit for dry mortarless installation
  • In lightweight partition walls, compartment walls, safety partition walls and radiation protection walls with metal support structures or steel support structures
  • In timber stud walls and timber frame walls, as well as solid wood and cross laminated timber walls
  • In shaft walls with metal support structure or steel support structure, and in shaft walls without metal support structure
  • In solid wood and wooden beam ceilings

Note:

For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

L [mm]

Order code

500

ES


Installation kit WA

  • Dry mortarless installation on the face of solid walls and ceiling slabs requires an installation kit

Note:

For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

L [mm]

Order code

500

WA



Installation kit WE 

Dry mortarless installation remote from solid walls or ceiling slabs (below the ceiling, with horizontal duct) or remote from lightweight partition walls with cladding on both sides and metal supports requires an installation kit

Ducts made of galvanised steel or stainless steel

Fire-resistant cladding provided by others

Note: 
For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

L [mm]

Order code

500

WE


Installation kit GL

  • Dry mortarless installation in lightweight partition walls, compartment walls and safety partition walls with metal support structure, cladding on both sides, and with flexible ceiling joint directly underneath solid ceiling slabs, requires an installation kit
  • The installation kits are adapted to the wall thickness or the width of the metal stud system

- GL100 for wall thickness 100 mm when using 50 mm profile width

- GL125 for wall thickness 125 mm when using 75 mm profile width

- GL150 for wall thickness 150 mm when using 100 mm profile width

- GL175 for wall thickness 175 mm when using 125 mm profile width

  • Drive side on the right (details for a different installation orientation are available upon request)

Note:

For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

L [mm]

Order code

500



GL100
GL125
GL150
GL175




Accessories 2 – cover grille

Application

  • If only one end is to be ducted on site, the other end must have a cover grille
  • Extension pieces are required for heights > 400 mm due to construction
  • Fire damper, cover grille and, if applicable, extension piece are factory assembled to form a unit
  • The free area of the cover grille is approx. 70%
  • The fixing holes in the cover grille and extension piece match those in the fire damper flanges
  • Cover grilles are also available separately

Materials and surfaces

  • Cover grilles and extension pieces (height-dependent) made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers)
  • Mesh aperture 10 mm × 10 mm, wire width 2 mm

The following applies to Germany:

  • If fire dampers are used as air transfer units, the national building regulations must be observed.
  • As a rule, the use of such air transfer units is limited to pressure ventilation systems.

Note:

For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual.

Operating side

Installation side

Order code

Casing length [mm]

Cover grille-A0

305 / 500

-Cover grille0A

500

Cover grilleCover grilleAA*

500

Cover grilleflexible connectorAS

500

flexible connectorCover grilleSA

500

Cover grilleCircular spigotAR

500

Circular spigotCover grilleRA

500

Cover grilleProfile connecting frameAF

305 / 500

Profile connecting frameCover grilleFA

500


* AA for FK2-EU as air transfer unit


Accessories 2 – Flexible connectors


Application

  • Ducting must be installed in such a way that it does not impose any significant loads on the fire damper in the event of a fire. Be sure to comply with the relevant national guidelines and regulations
  • As ducts may expand and walls may become deformed in the event of a fire, we recommend using flexible connectors for installation in lightweight partition walls, shaft walls and lightweight compartment walls, as well as fire batt installation.
  • Flexible connectors should be installed in such a way that both ends can absorb both tension and compression
  • Flexible ducts can be used as an alternative
  • For heights > 400 mm, extension pieces are required due to construction
  • The fixing holes in the flexible connectors and extension pieces match those in the fire damper flanges
  • Flexible connectors are also available separately


Materials and surfaces

  • Flexible connectors made of fibre-reinforced plastic and galvanised steel. Extension pieces (height-dependent) made of galvanised sheet steel (and powder-coated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers)
  • Fire resistance properties to 4102; B2


Note:

For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual. 

Operating side

Installation side

Order code

Casing length [mm]

flexible connector-S0

305 / 500

-flexible connector0S

500

flexible connectorflexible connectorSS

500

flexible connectorCover grilleSA

500

Cover grilleflexible connectorAS

500

flexible connectorCircular spigotSR

500

Circular spigotflexible connectorRS

500

flexible connectorProfile connecting frameSF

305 / 500

Profile connecting frameflexible connectorFS

500


Accessories 2 – Profile connecting frame


Application

  • Profile connecting frames are required for the connection of ducts using a sluice gate valve
  • Lower leakage rates can be achieved when profile connecting frames are installed than when using a flange screw connection.
  • Profile connecting frames have a sliding rebate. In addition to the 4-screw corner joints, the duct and profile connecting frame are connected by means of a sluice gate valve.
  • The fixing holes in the profile connecting frame match those in the fire damper flanges.
  • Profile connecting frames are also available separately


Materials and surfaces

Profile connecting frame made of galvanised steel

Note:
For further information relevant to design, in particular information on installation situations, please refer to the operating and installation manual. 

Operating side

Installation side

Order code

Casing length [mm]

Profile connecting frame-F0

305 / 500

-Profile connecting frame0F

305 / 500

Profile connecting frameProfile connecting frameFF

305 / 500

Profile connecting frameflexible connectorFS

500

flexible connectorProfile connecting frameSF

305 / 500

Profile connecting frameCover grilleFA

500

Cover grilleProfile connecting frameAF

305 / 500

Profile connecting frameCircular spigotFR

500

Circular spigotProfile connecting frameRF

305 / 500


Accessories 2 – Circular spigot


Application

  • Circular spigots for rectangular FK2-EU fire dampers facilitate the direct connection of circular ducts.
  • Extension pieces are required for heights > 400 mm due to construction
  • Circular spigots and, if applicable, extension pieces are factory assembled to form a unit.
  • The fixing holes in the round spigots match those in the fire damper flanges.
  • Round spigots are also available separately.

Materials and surfaces

  • Circular spigots made of galvanised sheet steel (and powdercoated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers) 

Operating side

Installation side

Order code

Casing length [mm]

Circular spigot-R0

305 / 500

-Circular spigot0R

500

Circular spigotCircular spigotRR

500

Circular spigotflexible connectorRS

500

flexible connectorCircular spigotSR

500

Circular spigotCover grilleRA

500

Cover grilleCircular spigotAR

500

Circular spigotProfile connecting frameRF

305 / 500

Profile connecting frameCircular spigotFR

500


Dimensions [mm]


Nominal size

B×H

øD

200

200 × 200

198

250

250 × 250

248

300

300 × 300

248

350

350 × 350

313

400

400 × 400

398

450

450 × 450

448

500

500 × 500

498

550

550 × 550

498

600

600 × 600

558

650

650 × 650

628

700

700 × 700

628

750

750 × 750

708

800

800 × 800

798


Accessories 2 – Extension pieces


Application

  • When there are cover grilles, circular spigots, flexible connectors, moulds, etc., you may have to use an extension piece for certain heights.
  • Fire dampers with flexible connectors, cover grilles and round spigots, including extension parts, are supplied (depending on height).
  • Extension pieces are also available separately


Materials and surfaces

Extension pieces made of galvanised sheet steel (and powdercoated silver grey, RAL 7001, when used with powder-coated (1) and stainless steel (2) dampers)

Note:

The movement of the damper blade must not be obstructed by any accessory. The distance between the tip of the open damper blade and any accessory (moulded part, etc.) must be at least 50 mm.

Open blade protrusion [mm]

H

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

x

-204

-179

-154

-129

-104

-79

-54



-29 *




-4 *




21 *




46 *




71 *




96 *




121 *




146 *


y (1)



-8 *




17 *




42 *




67 *




92 *




117 *




142 *




167 **




192 **




217 **




242 **




267 **




292 **




317 **




342 **


y (2)

-204

-179

-154

-129

-104

-79

-54



-29 *




-4 *




21 *




46 *




71 *




96 *




121 *




146 *



* 1 *Extension piece required
** 2 Extension pieces required
(1) L = 305 mm
(2) L = 500 mm

Arrangement of extension pieces



L [mm]




H [mm]


Operating side

Installation side

305

100 – 400

195

305

405 – 800

195

2 × 195

500

100 – 400

500

405 – 800

195

195


Attachment – Limit switch

FK2-EU (fusible link construction) with limit switch Application

  • Limit switches with volt-free contacts can indicate the damper blade position
  • Up to the maximum switch rating, relays or indicator lights for fire alarm systems can be used
  • One limit switch each is required for damper blade positions OPEN and CLOSED
  • Fire dampers with a fusible link can be supplied or retrofitted with one or two limit switches (a conversion kit is required for a retrofit).
  • For the technical data and wiring examples, see the installation and operating manual for FK2-EU. 

Attachment

Order code

Limit switch for damper blade position CLOSEDZ01
Limit switch for damper blade position OPENZ02
Limit switches for damper blade positions CLOSED and OPENZ03


FK2-EU (fusible link construction) with limit switch in explosion-proof construction

Application

  • Explosion-proof limit switches with volt-free contacts can indicate the damper blade position
  • Declaration of conformity: EPS 20 ATEX 2 058 X
  • Up to the maximum switch rating, relays or indicator lights for fire alarm systems can be used
  • The limit switches must be connected in a separately approved casing with a type of protection according to EN 60079-0
  • One limit switch each is required for damper blade positions OPEN and CLOSED
  • Fire dampers with a fusible link can be supplied or retrofitted with one or two limit switches (a conversion kit is required for a retrofit).
  • Technical data and wiring examples, see additional operating manual "Explosion-protected fire dampers, type FK2-EU" 

Attachment

Order code

Limit switch for damper blade position CLOSEDZ01EX
Limit switch for damper blade position OPENZ02EX
Limit switches for damper blade positions CLOSED and OPENZ03EX

Type of actuation

Release mechanism

Labelling

Ambient temperature

maximum airflow velocity

Spring mechanismFusible linkII 2G Ex h IIC T6 Gb

II 2D Ex h IIIC T80°C Db
-40 – 40 °C8 m/s
Spring mechanismFusible link and limit switchII 2G Ex h IIC T6 Gb

II 2D Ex h IIIC T80°C Db
-20 – 40 °C8 m/s


Attachment – spring return actuator

FK2-EU with spring return actuator

Application

  • A spring return actuator allows for the remote control of the fire damper and/or release by a suitable duct smoke detector
  • If the supply voltage fails, or with thermoelectric release, the damper closes (power off to close)
  • Motorised fire dampers can be used to shut off ducts
  • Two integral limit switches with volt-free contacts can indicate the damper blade position (OPEN and CLOSED)
  • The connecting cables of the 24 V spring return actuator are fitted with plugs. This ensures quick and easy connection to the TROX AS-i bus system. Without automation components, the 24 V connection is made via a safety transformer provided by others
  • A conversion kit is available for retrofitting an actuator to a fire damper with fusible link.
  • For the technical data and wiring examples, see the installation and operating manual for FK2-EU. 

Attachment

Order code

Spring return actuator 230 V (Belimo)Z43 
Spring return actuator 24 V (Belimo)Z45 
Spring return actuator 24 V (Belimo) including power supply unit BKN230-24-C-MP TRZ60 
Spring return actuator 24 V (Belimo) including power supply unit BKN230-24-C-MP TR and control module BKS24-1 TRZ61 
Spring return actuator 230 V (Siemens)Z43S
Spring return actuator 24 V (Siemens)Z45S

 
Attachment – explosion-proof spring return actuator

FK2-EU with explosion-proof spring return actuator 

Application

  • A spring return actuator allows for the remote control of the fire damper and/or release by a suitable duct smoke detector
  • The fire damper can be used in supply and extract air systems in areas with potentially explosive atmospheres
  • If the supply voltage fails, or with thermoelectric release, the damper closes (power off to close)
  • Fire dampers with spring return actuators can be functionally checked OPEN/CLOSED/OPEN
  • Two integral limit switches with volt-free contacts can indicate the damper blade position (OPEN and CLOSED)
  • The electrical connection is made in the explosion-proof terminal box
  • Release temperature of the spring return actuator 72 °C
  • Declaration of conformity: EPS 20 ATEX 2 058 X
  • Technical data and wiring examples, see additional operating manual "Explosion-protected fire dampers, type FK2-EU"

Use in areas with potentially explosive atmospheres (ATEX)

According to declaration of conformity EPS 20 ATEX 2 058 X, the fire damper may be used in the following areas with potentially explosive atmospheres.

The ambient temperatures and types of release and actuation specified in the technical data are binding.

ExMax:
Zones 1, 2: Gases, mists and vapours

Zones 21, 22: Dusts

RedMax:

Zone 2: Gases, mists and vapours

Zone 22: Dusts 

Attachment

Order code

ExMax-15-BF TRZEX1
RedMax-15-BF TRZEX3

Type of actuation

Release mechanism

Labelling

Ambient temperature

maximum airflow velocity

ExMax-15-BF TRExPro-TT *II 2G Ex h IIC T6 Gb

II 2D Ex h IIIC T80°C Db
-40 – 40 °C10 m/s
RedMax-15-BF TRExPro-TT *II 3G Ex h IIC T6 Gc

II 3D Ex h IIIC T80°C Dc
-40 – 40 °C10 m/s

* Release temperature: 72 °C


Attachment – Spring return actuator and RM-O-3-D

FK2-EU with spring return actuator and duct smoke detector RM-O-3-D

Application

  • An open/close actuator allows for remote control of the fire damper and/or release by a suitable duct smoke detector
  • If the supply voltage fails, or with thermoelectric release or smoke detection the damper closes (power off to close)
  • Motorised fire dampers can be used to shut off ducts.
  • Two integral limit switches with volt-free contacts can indicate the damper blade position (OPEN and CLOSED)
  • The type RM-O-3-D duct smoke detector must be installed in the lower inspection access and arranged at the top when assembling the fire damper.
  • For the technical data and wiring examples, see the installation and operating manual for FK2-EU and/or the operating and installation manual for duct smoke detector type RM-O-3-D. 

Attachment

Order code

With spring return actuator 230 V (Belimo) and integrated duct smoke detector type RM-O-3-DZ43RM
With spring return actuator 24 V (Belimo) and integrated duct smoke detector type RM-O-3-DZ45RM
With spring return actuator 230 V (Siemens) and integrated duct smoke detector type RM-O-3-DZ43RMS
With spring return actuator 24 V (Siemens) and integrated duct smoke detector type RM-O-3-DZ45RMS


Attachment – Spring return actuator and TROXNETCOM

FK2-EU with spring return actuator and TROXNETCOM

Application

  • Fire dampers with a 24 V spring return actuator (Belimo) and the modules described here as attachments form a functional unit ready for automatic operation.
  • The components are factory assembled and wired
  • The combination spring return actuator with TROXNETCOM enables brand-neutral and cross-sector integration of various components (modules) in one network
  • The modules control actuators and/or receive signals from sensors

AS-i

  • AS interface is a global standard bus system according to EN 50295 and IEC 62026-2.
  • The module transmits the control signals between the spring return actuator and the controller and power unit
  • The control of the actuator and monitoring of run time for functional tests is thus possible
  • The voltage (24 V DC) for the module and the actuator is supplied via the two-wire AS-i flat cable
  • Function display: operation, 4 inputs, 2 outputs


MODBUS RTU/BACnet MS/TP (RS485)

  • MODBUS RTU and BACnet MS/TP are protocols for RS485 communication systems
  • Data transmission is based on uniform protocols
  • Only the bus line and the supply voltage remain to be connected by others
  • MB-BAC-WA1/2: for the control of 1 – 2 fire dampers
  • WA1/B3-AD: junction box for the 2nd fire damper with 24 V DC supply voltage to the MB-BAC-WA1/2
  • WA1/B3-AD230: junction box with integrated power supply unit 230/24 V for connection of a 2nd motor-driven 24 V fire damper to the MB-BAC-WA1/2 LON

LON

  • LON indicates a standard local operating network system with manufacturer-independent communications
  • Data transmission is based on a uniform protocol
  • LonMark defines standards to ensure product compatibility
  • Only the bus line and the supply voltage remain to be connected by others
  • LON-WA1/B3: for the control of 1 – 2 fire dampers
  • WA1/B3-AD: junction box for the 2nd fire damper with 24 V DC supply voltage to the LON-WA1/B3
  • WA1/B3-AD230: junction box with integrated power supply unit 230/24 V for the connection of a second motor-driven 24 V fire damper to the LON-A1/B3 TNC-EASYCONTROL


TNC-EASYCONTROL

  • TNC-LINKBOX is a wiring aid for connecting a fire damper and the configurable parallel circuit for the TNC-EASYCONTROL decentralised operating and monitoring system. 

Attachment

Order code

Spring return actuator 24 V and AS-EMZA07
Spring return actuator 24 V, RM-O-3-D and AS-EMZA12
Spring return actuator 24 V and MB-BAC-WA1/2ZB01
Spring return actuator 24 V and LON-WA1/B3ZL09
Spring return actuator 24 V and WA1/B3-ADZL10
Spring return actuator 24 V and WA1/B3-AD230ZL11
Spring return actuator 24 V and TNC-LinkboxZA14
Spring return actuator 24 V and MB-BAC-WA1/2ZB01

 

Attachment – Duct smoke detectors

Application

  • To prevent smoke from spreading in buildings, it is extremely important that the smoke is detected at an early stage.
  • Duct smoke detectors that operate on the principle of light scattering detect the smoke regardless of its temperature so that the fire dampers can be closed before the release temperature of 72 °C is reached
  • If the air contains suspended particles, as is the case with smoke, beams of light are deflected off these. A sensor (photodiode), which does not receive light in clear air, is illuminated by the scattered light.
  • The fire damper or smoke protection damper blade is released when the brightness of the scattered light exceeds a certain threshold

Attachment

Order code

Duct smoke detector

RM-O-3-D

RM-O-VS-D


Duct smoke detectors are attachments and to be ordered separately.

RM-O-3-D can also be supplied assembled and wired for FK2-EU with standard application.



Downloads

product information

brochures

certificates

operation manuals

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Contact

We are here for you

Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051