img_pro_000548.png
Mini Pleat filter panels for clean room technology, type MFPCR

doc_graphic_000009.png
Tested to VDI 6022

Conforms to VDI 6022

img_pro_000548.png
doc_graphic_000009.png

MFPCR

For the most demanding requirements on the purity of indoor air, workstations, and devices


 

HEPA and ULPA filters as high-efficiency particulate filters for the separation of suspended particles in clean room systems. Used for industrial, research, medical, pharmaceutical, and nuclear engineering applications.

  • Filter classes H14, U15, U16
  • Performance tested in accordance with EN 1822-1 and ISO 29463-2 to ISO 29463-5
  • Meets the hygiene requirements of VDI 6022
  • Filter media for special requirements, glass fibre papers with spacers made of thermoplastic hot-melt adhesive
  • Low initial differential pressure due to ideal pleat position and largest possible filter area
  • Perfect adjustment to individual requirements due to variable pleat depths
  • Fitting into filter fan units, clean room workbenches, or operating theatre ceilings
  • Automatic filter scan test

 

 

 


Introduction

Application


  • Mini Pleat filter panel type MFPCR for the separation of suspended particles such as aerosols, toxic dusts, viruses, bacteria from the supply and extract air in clean room systems with controlled air cleanliness and airflow.
  • Particulate filters: Final filters for the most critical requirements of air cleanliness and sterility in areas such as production, research, medicine, pharmaceuticals industry, and nuclear engineering

Special characteristics


  • Ideal pleat geometry of the filter medium
  • Low-turbulence airflow on the downstream side
  • Filter scan test ensures leak-free construction as well as compliance with the stated efficiency and differential pressure

Classification

  • Meets the hygiene requirements


Nominal sizes

▪ B × H × D [mm]

Description

Filter classes
Filter groups

  • HEPA according to EN 1822
  • ULPA according to EN 1822

Filter classes

  • H14
  • U15
  • U16


Options

  • FT: Pleat depth
  • PU: Protection grid on the upstream side
  • PD: Protection grid on the downstream side
  • PB: Protection grid on both sides
  • CSU: Continuous seal on the upstream side
  • CSD: Continuous seal on the downstream side
  • CSB: Continuous seal on both sides
  • OT: Oil mist test (only for filter class H14)
  • LFU: Full-surface laminator fleece on the upstream side
  • LFU: Full-surface laminator fleece on the downstream side
  • LFS: Laminator fleece strip

Construction

  • ALB: Frame made of extruded aluminium sections (depth 69 mm)
  • ALC: Rahmen Aluminium-Strangpressprofil (Tiefe 78 mm)
  • ALG: Frame made of extruded aluminium sections (depth 90 mm)

Construction features

▪ Perimeter continuous seal on the upstream side as standard
▪ Some constructions with optional continuous seal on thedownstream side or on both sides
▪ Protection grid made of expanded metal, can be fitted on thedownstream or upstream side or both sides as required

Materials and surfaces
▪ Filter media made of high-quality, moisture-resistant glassfibre papers, pleated
▪ Spacers made of thermoplastic hot-melt adhesive provide auniform spacing of the pleats
▪ Joint sealing compound made of permanently elastic two-component polyurethane adhesive
▪ Frame made from extruded aluminium sections


Standards and guidelines
▪ Testing of particulate filters to 1822-1 and ISO 29463-2 toISO 29463-5 (EPA, HEPA and ULPA particulate filters):European standard for the testing of filtration performance inthe factory, particle counting method using a liquid testaerosol
▪ Uniform classification of particulate filters according toefficiency, using a test aerosol whose average particle sizelies within the minimum efficiency (MPPS)
▪ Particulate filters are classified according to the valuesdetermined for the local filtration efficiency and the overallfiltration efficiency as EPA (filter classes E10, E11, E12),HEPA (filter classes H13, H14) or ULPA (filter classes U15,U16, U17)
▪ Hygiene meets the requirements of VDI 6022, VDI 3803,DIN 1946 Part 4, ÖNORM H 6021 and ÖNORM H 6020,SWKI VA 104-01 and SWKI 99-3, and EN 16798


Technical information

Technical data, Specification text, Order code

  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE

Filter class according to EN 1822H14U15U16
Efficiency [%] according to EN 1822> 99.995 %> 99.9995 %> 99.99995 %
Nominal face velocity [m/s]0.450.450.45
Initial differential pressure [Pa] at nominal face velocity for frame ALB110130
Initial differential pressure [Pa] at nominal face velocity for frame ALC95115140
Initial differential pressure [Pa] at nominal face velocity for frame ALG85100120
Max. operating temperature [°C]808080
Maximum relative humidity [%]100100100



Specification text
Mini Pleat filter panels MFPCR for the separation of suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply and extract air in clean room systems with controlled air cleanliness and airflow. Use as particulate filters, i.e. main or final filters, for the most critical requirements of air cleanliness and sterility in areas such as industry, research, medicine, pharmaceuticals, and nuclear engineering. Mini Pleat filter plates for clean room technology, consisting of an extruded aluminium frame, filter media of high-quality, moisture-resistant glass fibre papers with spacers made of thermoplastic hot-melt adhesive. Different pleat depths enable perfect adjustment to individual requirements. Mini Pleat filter panels for clean room technology available in standard and special sizes, filter classes H14, U15, U16. As standard, Mini Pleat filter panels for clean room technology are fitted with a perimeter continuous seal on the upstream side. Some constructions are available with an optional seal on the downstream side or on both sides, or with a protection grid (arrangement as required) and full-surface laminator fleece or laminator fleece strip. As standard, Mini Pleat filter panels for clean room technology are subjected to an automatic filter scan test.



Special characteristics

  • Ideal pleat geometry of the filter medium
  • Low-turbulence airflow on the downstream side
  • Filter scan test ensures leak-free construction as well as compliance with the stated efficiency and differential pressure

Materials and surfaces
▪ Filter media made of high-quality, moisture-resistant glassfibre papers, pleated
▪ Spacers made of thermoplastic hot-melt adhesive provide auniform spacing of the pleats
▪ Joint sealing compound made of permanently elastic two-component polyurethane adhesive
▪ Frame made from extruded aluminium sections

Construction
▪ ALB: Frame made of extruded aluminium sections (depth69 mm)

▪ ALC: Rahmen Aluminium-Strangpressprofil (Tiefe 78 mm)
▪ ALG: Frame made of extruded aluminium sections (depth90 mm)

Sizing data
▪ Filter class [EN 1822]
▪ Volume flow rate [m³/h]
▪ Initial differential pressure [Pa]
▪ Nominal size [mm]




MFPCRH14ALC / 1220 × 610 × 78×58 / PD / CSU / ST / LFU
|||||||||
123456789

1 Type
MFPCR Mini Pleat filter panel for clean room technology
 
2 Filter class
H14 Particulate filter according to EN 1822
U15 Particulate filter according to EN 1822
U16 Particulate filter according to EN 1822
 
3 Construction
ALB Frame made of extruded aluminium sections (depth 69 mm)
ALC Frame made of extruded aluminium sections (depth 78 mm)
ALG Frame made of extruded aluminium sections (depth 90 mm)
 
4 Nominal size [mm]
B × H × T
 
5 Pleat depth [mm]
FT
 
6 Protection grid
No entry: none
PU Protection grid on the upstream side
PD Protection grid on the downstream side
PB Protection grid on both sides
 
7 Seal
CSU Continuous seal on the upstream side
CSD Continuous seal on the downstream side
CSB Continuous seal on both sides
 
8 Testing
ST Scan test
 
9 Laminator
No entry: none
LFU Full-surface laminator fleece on the upstream side
LFD Full-surface laminator fleece on the downstream side
LFS Laminator fleece strip

MFPCR–H14–ALC/1220×610×78×58/PD/CSU/ST
Filter class H14 particulate filter according to EN 1822
Construction frame made of extruded aluminium sections (depth 78 mm)
Nominal size 1220 × 610 × 78 mm
Pleat depth 58
Protection grid downstream side
Seal Continuous seal on the upstream side
Test scan test

   

Dimensions

  • Dimensions
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053056950H14421501102,81
4574576950H14943401106,32
3056106950H14833001105,72
4576106950H141254501108,53
6106106950H1416860511011,24
7626106950H14210755110144
9156106950H1425190511016,85
12206106950H14335120511022,36
15256106950H14418150511027,88
18306106950H14503181011033,39
7627626950H1426194011017,55
9157626950H143141130110215
12207626950H14418150511027,97
15257626950H14522188011034,89
18307626950H14628226011041,710
9159156950H14376135511025,26
12209156950H14501180511033,58
15259156950H14628226011041,910
18309156950H14753271011050,212
3053056950U15421501302,81
4574576950U15943401306,32
3056106950U15833001305,72
4576106950U151254501308,53
6106106950U1516860513011,24
7626106950U15210755130144
9156106950U1525190513016,85
12206106950U15335120513022,36
15256106950U15418150513027,88
18306106950U15503181013033,39
7627626950U1526194013017,55
9157626950U153141130130215
12207626950U15418150513027,97
15257626950U15522188013034,89
18307626950U15628226013041,710
9159156950U15376135513025,26
12209156950U15501180513033,58
15259156950U15628226013041,910
18309156950U15753271013050,212
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053057858H1442150953,32
4574577858H1494340957,33
3056107858H1483300956,63
4576107858H14125450959,83
6106107858H1416860595134
7626107858H142107559516,25
9156107858H142519059519,45
12206107858H1433512059525,97
15256107858H1441815059532,39
18306107858H1450318109538,710
7627627858H142619409520,35
9157627858H1431411309524,36
12207627858H1441815059532,48
15257627858H1452218809540,410
18307627858H1462822609548,412
9159157858H1437613559529,37
12209157858H1450118059538,99
15259157858H1462822609548,612
18309157858H1475327109558,214
3053057858U15421501153,32
4574577858U15943401157,33
3056107858U15833001156,63
4576107858U151254501159,83
6106107858U15168605115134
7626107858U1521075511516,25
9156107858U1525190511519,45
12206107858U15335120511525,97
15256107858U15418150511532,39
18306107858U15503181011538,710
7627627858U1526194011520,35
9157627858U15314113011524,36
12207627858U15418150511532,48
15257627858U15522188011540,410
18307627858U15628226011548,412
9159157858U15376135511529,37
12209157858U15501180511538,99
15259157858U15628226011548,612
18309157858U15753271011558,214
3053057858U16421501403,32
4574577858U16943401407,33
3056107858U16833001406,63
4576107858U161254501409,83
6106107858U16168605140134
7626107858U1621075514016,25
9156107858U1625190514019,45
12206107858U16335120514025,97
15256107858U16418150514032,39
18306107858U16503181014038,710
7627627858U1626194014020,35
9157627858U16314113014024,36
12207627858U16418150514032,48
15257627858U16522188014040,410
18307627858U16628226014048,412
9159157858U16376135514029,37
12209157858U16501180514038,99
15259157858U16628226014048,612
18309157858U16753271014058,214
,
B [mm]H [mm]T [mm]Pleat depthFilter classqv [l/s]qv [m³/h]ΔpA [Pa]kg
3053059070H1442150853,82
4574579070H1494340858,63
3056109070H1483300857,73
4576109070H141254508511,53
6106109070H141686058515,25
7626109070H142107558518,95
9156109070H142519058522,76
12206109070H1433512058530,28
15256109070H1441815058537,610
18306109070H1450318108545,112
7627629070H142619408523,76
9157629070H1431411308528,47
12207629070H1441815058537,89
15257629070H1452218808547,112
18307629070H1462822608556,614
9159159070H1437613558534,18
12209159070H1450118058545,410
15259159070H1462822608556,614
18309159070H1475327108567,916
3053059070U15421501003,82
4574579070U15943401008,63
3056109070U15833001007,73
4576109070U1512545010011,53
6106109070U1516860510015,25
7626109070U1521075510018,95
9156109070U1525190510022,76
12206109070U15335120510030,28
15256109070U15418150510037,610
18306109070U15503181010045,112
7627629070U1526194010023,76
9157629070U15314113010028,47
12207629070U15418150510037,89
15257629070U15522188010047,112
18307629070U15628226010056,514
9159159070U15376135510034,18
12209159070U15501180510010
15259159070U15628226010056,614
18309159070U15753271010067,916
3053059070U16421501203,82
4574579070U16943401208,63
3056109070U16833001207,73
4576109070U1612545012011,53
6106109070U1616860512015,25
7626109070U1621075512018,95
9156109070U1625190512022,76
12206109070U16335120512030,28
15256109070U16418150512037,610
18306109070U16503181012045,112
7627629070U1626194012023,76
9157629070U16314113012028,47
12207629070U16418150512037,89
15257629070U16522188012047,112
18307629070U16628226012056,514
9159159070U16376135512034,18
12209159070U16501180512045,410
15259159070U16628226012056,614
18309159070U16753271012067,916

Downloads

product information

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Contact

We are here for you

Please specify your message and type of request.
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +44 (0)1842 754545 | Fax: +44 (0)1842 763051