POOL: TCU-LON-II controller with LON interface

LABCONTROL-LON system


Brief Description

The digital controller TCU-LON-II (control component TMA, TQA, TM0) was designed for highly demanding control tasks. The system can be adapted to the area of application by means of various types of operation (software) as well as configuration settings stored in the controller. Thus the system is able to perform the various tasks required of a room supply air, exhaust air or fume hood controller.

TCU-LON-II_2_240
TCU-LON-II_1_240
TVLK_4_240

  • Evaluation of measured volume flow and damper actuation

  • Application area fume hood and room control

  • Rapid and stable volume flow control (response time <= 3 seconds)

  • Exchange of volume flow values via LON interface

  • Full data access and system configuration via LON interface

  • Configurable I/O interfaces

  • Individul adaption to project specifications



Information for commissioning of LON components
The actual volume flow is recorded using a membrane pressure transmitter by means of the differential pressure method. For long-term stabilisation of the measurement, the standard scope of delivery includes an automatic zero-point compensation procedure. This ensures that the measurements will be continued to be exact, even at low differential pressures. The measured volume flows are evaluated and, in accordance with the control algorithm, cause the damper in the volume flow controller to be adjusted by the connected continuous actuator. The controller acts rapidly and stably, and the response time is less than 3 seconds. At fume hoods, the current operating state is indicated on a control panel

The exchange of actual volume flow values with other control systems only takes place by means of standard network variables (SNVT) via the LON bus.

To meet the demands of a variable and diverse control mechanism, the system is equipped with configurable I/O interfaces in addition to the LON interface.

TCU-LON-II controller


  • Integrated membrane pressure transmitter with zeroing valve
    for long-term stabilisation of the measurement


  • LON bus interface physically implemented via FTT10A transceiver
    - With double terminals for simple installation
    - Service button for transmission of Neuron ID during commissioning


  • LON bus data interface via standard network variable types (SNVT)
    - Configuration of all settings for controller operation and software update
    - Visibility of all actual values, current set values, types of operation and settings
    - Swichting the operation type via LON or digital inputs with priority classification
    - Alarm messages via LON / digital output


  • 2 Digital inputs for potential-free contacts, e.g. for
    - Switching between day / night / full shut-off operation with switches
    - Integration of contact for detection of 500 mm window opening as per DIN 14175
    - Integration of a motion sensor


  • 1 Digital output as a switching contact (changeover relay)
    - Changeover contacts, e.g. for conventional alarm forwarding to BMS systems


  • 1 Analogue input for 0-10 V or 2-10 V signals
    - System usage fume hood controller: Input occupied by velocity sensor
    - System usage pressure controller: Input occupied by pressure transmitter
    - System usage room controller: Input for applying 0-10 V signal e.g. volume flow


  • 1 Analogue output for 0-10 V or 2-10 V signals
    Occupied by the actuator of the controller


  • Slot for standard control panel of TCU-LON-II system
    Expanded control panel AF-1 only in combination with certain control components


  • Supply voltage 24 V AC/DC
    with double terminals for simple installation



Information for commissioning of LON components
Name Group Type Ident-No. Type/Size
         
TCU-LON-II Controller LABCONTROL-LON Technical Information E016BQ2 PDF / 598 KB 
TCU-LON-II - SNVT list fume hood LABCONTROL-LON Technical Information - PDF / 15 KB 
TCU-LON-II - SNVT list room control LABCONTROL-LON Technical Information PDF / 18 KB 

Air management systems

Overview brochures

The LABCONTROL Air management systems - An introduction into system characteristics, components and typical application areas

Installation examples

Tailor-made solutions

the air management system LABCONTROL

More ...

Contact

TROX GmbH

Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn
Tel: +49 (0)2845 / 202-0
Contact and locations