search-loading

POOL: Room supply/exhaust air controller - TVR

with LABCONTROL and the LON communication system


The area of application of the TVR is in variable volume flow systems for supply and exhaust air. It can be used there as a volume flow controller for room pressure and as a channel pressure controller.

TVR
  • Variable volume flow controller for supply / exhaust air

  • Nominal width Ø 100 - 400 mm

  • Total length approx. 600 mm

  • For medium to low acoustic requirements

  • Volume flow range 43 - 6048 m³/h

  • Full air-tight shut-off as per DIN EN1751 Class 4 or 3

  • For the LABCONTROL-LON system, the TVR is combined with the TMA control component which is based on the TCU-LON-II controller.


    More technical data

    • Round connections on both sides, deliverable with flange/mating flange on request
    • Housing and ancillary component parts made of galvanised steel sheet
    • Surface optionally available with powder coating (TVR-P1)
    • Optionally available with acoustic cladding for high acoustic requirements (TVRD)
    • Differential pressure range 20 to 1500 Pa
    • Supply voltage 24 V AC
    • Connected load 25 VA
    • Protection type IP 20

    Name Group Type Ident-No. Type/Size
             