search-loading

POOL: Room pressure control

Definable pressure conditions for sensitive areas with LABCONTROL-ANALOGUE


In highly sensitive areas such as in hospitals, cleanrooms, animal housing and rooms with stringent hygienic and safety requirements, high demands are place on air handling systems. For hygienic reasons, the air between rooms may only flow in one direction, namely from rooms with higher demands to rooms with lower demands.

The TROX VAV controllers with the LABCONTROL TRA-PS or TRA-PE control component for room supply / exhaust air control and additional room pressure control offer a wide range of possibilities. By supplementing this controller with an external room pressure transmitter, the control of the volume flow balance in the room can be enhanced by a definable pressure control. The current measured room pressure is connected by an analogue signal to the room controller. Any deviation from the set value is corrected by shifting the supply / exhaust air difference.

The room pressure control is in cascade with the volume flow while taking into account the volume flow balance. This results in stable control, even when the volume flow conditions change rapidly and when doors are opened and closed.

hospital_240
  • Room pressure control with LABCONTROL control components TRA-PS (Supply air) or TRA-PE (Exhaust air)

  • Definable room pressure conditions for sensitive areas

  • Configurable room over/under pressure

  • Changeover between over/under pressure with potential free switching contact

  • Stable control - No door contacts required




  • Optionally, an additional and independent monitoring of the pressure control can be implemented by employing a LABCONTROL monitoring unit of type TPM.






    Optionally, an additional and independent monitoring of the pressure control can be implemented by employing a LABCONTROL monitoring unit of type TPM.

     

    Name Group Type Ident-No. Type/Size
             
    Product overview - Room air control LABCONTROL Technical Information 11/2008 PDF / 112 KB 
    TCU-II LABCONTROL-ANALOG Technical Information PI/7.4/1/D/1 PDF / 2.5 MB 

    Air management systems

    Overview brochures

    The LABCONTROL Air management systems - An introduction into system characteristics, components and typical application areas

    Installation examples

    Tailor-made solutions

    the air management system LABCONTROL

    More ...

    Contact

    TROX GmbH

    Heinrich-Trox-Platz
    D-47504 Neukirchen-Vluyn
    Tel: +49 (0)2845 / 202-0
    Contact and locations