The actual volume flow is recorded using a membrane pressure transmitter by means of the differential pressure method. For long-term stabilisation of the measurement, the standard scope of delivery includes an automatic zero-point compensation procedure. This ensures that the measurements will be continued to be exact, even at low differential pressures.
The measured volume flows are evaluated and, in accordance with the control algorithm, cause the damper in the volume flow controller to be adjusted by the connected continuous actuator. The controller acts rapidly and stably, and the response time is less than 3 seconds. At fume hoods, the current operating state is indicated on a control panel.
The exchange of actual volume flow values with other systems only takes place via analogue 0-10 V signals.
To meet all the demand placed on a variable and diverse control mechanism, the system is equipped with numerous configurable I/O interfaces.
The measured volume flows are evaluated and, in accordance with the control algorithm, cause the damper in the volume flow controller to be adjusted by the connected continuous actuator. The controller acts rapidly and stably, and the response time is less than 3 seconds. At fume hoods, the current operating state is indicated on a control panel.