Brief Description

The digital controller TCU-II (control component TRA, TUA, TR0) was designed for highly demanding control tasks. The system can be adapted to the area of application by means of various types of operation (software) as well as configuration settings stored in the controller. Thus the system is able to perform the various tasks required of a room supply air, exhaust air or fume hood controller.

TCU-II-Platine_240
TCU-II_240
TVLK_240

  • Evaluation of measured volume flow and damper actuation

  • Application area fume hood and room control

  • Rapid and stable volume flow control (response time <= 3 seconds)

  • Exchange of volume flow values via analogue 0-10 V signals

  • Numerous configurable I/O interfaces

  • Individul adaption to project specifications


System configuration with TROX LabConnect software
The actual volume flow is recorded using a membrane pressure transmitter by means of the differential pressure method. For long-term stabilisation of the measurement, the standard scope of delivery includes an automatic zero-point compensation procedure. This ensures that the measurements will be continued to be exact, even at low differential pressures.
The measured volume flows are evaluated and, in accordance with the control algorithm, cause the damper in the volume flow controller to be adjusted by the connected continuous actuator. The controller acts rapidly and stably, and the response time is less than 3 seconds. At fume hoods, the current operating state is indicated on a control panel.

The exchange of actual volume flow values with other systems only takes place via analogue 0-10 V signals.

To meet all the demand placed on a variable and diverse control mechanism, the system is equipped with numerous configurable I/O interfaces.

TCU-II controller


  • Integrated membrane pressure transmitter with zeroing valve
    for long-term stabilisation of the measurement


  • 3 Digital inputs for potential-free contacts, e.g. for
    - Switching between types of operation day / night operation / full shut-off
    - Integration of a contact for window opening 500 mm as per DIN 14175
    - Integration of a motion sensor


  • 5 Digital outputs as switching contacts (4 closer relays, 1 changeover relay)
    - Changeover contacts, e.g. alarm forwarding to building management systems
    - Make contacts, e.g. for light control, window closing unit


  • 7 Analogue inputs for 0-10 V or 2-10 V signals
    - TCU-II usage fume hood controller:
    one input is occupied by velocity sensor
    remaining inputs can be used for summation of volume flows
    - TCU-II usage pressure controller:
    one input is occupied by the pressure transmitter


  • 4 Analogue outputs for 0-10 V or 2-10 V signals
    - 1 analogue output is occupied by the actuator of the controller
    - 3 analog outputs, e.g. for actual volume flow values


  • Socket for standard control panel or expanded control panel AF-1


  • Socket for service/configuration PC
    for configuration with LabConnect software and software update


  • Supply voltage 24 V AC / DC
    with easy-to-install double terminals



System configuration with TROX LabConnect software
Downloads Group Type Ident-No. Type / Size
         
TCU-II LABCONTROL-ANALOG Technical Information PI/7.4/1/D/1 PDF / 2.5 MB 

Air management systems

Overview brochures

The LABCONTROL Air management systems - An introduction into system characteristics, components and typical application areas

Installation examples

Tailor-made solutions

the air management system LABCONTROL

More ...

Contact

TROX GmbH

Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn
Tel: +49 (0)2845 / 202-0
Contact and locations